DF PROFINET IO | GettingStarted: Input / Output status are “Bad”
DF PROFINET IO | GettingStarted: Input / Output status are “Bad”
back to FAQs
Issue: | Additional information |
After starting the Controller or Device of the board. The Input or Output Status is “Bad” even if the APDU status shows 0x35. | Hardware:
Software:
|
Solution: |
|
Set the Output Data initially from the controller and set the Input Data initially from the Device. This activates the PROFINET cyclic data communication. |
|
, multiple selections available,