I have a problem to load a GSDML file into the Configurator III

  • You can check the GSDML file with the “GSDML-Checker” tool.
    The software can be downloaded from the following link:
    https://de.profibus.com/downloads/profinet-gsd-checker

  • download the original file directly from the manufacturer's website to ensure that it hasn't been modified or updated by the PLC.


I need the Kunbus Configurator III. Via Google there are still some links to your website. However, these lead to nowhere in the meantime.

  • The "Configurator III" software must currently be provided manually.

  • Please send us an e-mail to support@kunbus.com

Is the configuration of the DF Profinet IO card as a device also created with the Configurator III?

No, always via the controller e.g. Siemens controller, configuration creation e.g. via TIA with the GSDML of the DF Profinet IO card.

I get this error and the configuration cannot be downloaded. What can I do?

  • Please update your Configurator III software to the latest version which is version 3.1.2.

  • This software is provided by the WINDOWS Device Drivers. Please contact support@kunbus.com for the provision of a download.

  • In case the problem still exists with the latest software then please send us the following file

  • C:\ProgramData\Configurator3\ABM_TO_DFXX.log

Is it possible to transfer the configuration of a measuring card already in operation to the KUNBUS Configurator III?

  • No unfortunately this is not possible.

  • Please create a configuration. Please click on the link for a short video demonstration how it works:

Definition of online device status in Configurator III

Frame Color of Device

Reason

Solution

RED

Device is not reachable in online mode by the controller.

Please verify that:

  • a proper physical connection between controller and device is established.

  • GSDML choice relates to the exact physical device in your network setup.

  • device is switched on and runs.

BLUE

Device is been detected online. It relates to the choice of the selected GSDML item, but its (I/O)-properties differs.
I/O-configuration of the slots of configured device and the one of real device does not match.

  • So the (I/O configuration of the device/slave) is not correct. The device is been detected (address and name are OK), but it is not configured according to its real sibling.

    • E.g: 4 IN | 16 OUT in controller/master configured, but a device/slave with 4 IN | 4 OUT connected and found.

  • Please configure the I/O slots according to the I/O setup of your real device!

GREEN

Device is been detected in online mode and communication runs properly.

  • configuration is OK

How to configure the KUNBUS network configurator?

In the following video, you can see how to configure the KUNBUS network configurator.