DF PROFINET IO | Getting Started (Q+A) - Windows driver

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 9 Current »

Caption:

  • Question

    • Solution


  • The two device ports still as above, basic device example software started an choice 4 active. If I do not do this the controller finds no devices.

    • An application has to be run on your Profinet-Device, else your device would not be visible since the Profinet-FW is not running on it.

    • That affects any Profinet-Device from any provider.

    • see Kunbus Example Clip below


  • Controller port has IP 192.168.20.1. How can I verify what the IP of the control port actually is without using some external PC / router /…. ?



  • Every device has to be configured with I/O-Modules in its slots(at least one). What do you mean by slot ?

    • It is necessary to add IN- and/or OUT-Modules to a device to complete its configuration.



  • I get red light on all 3 KUNBUS board ports and “Bad By SubSlot” when I try to monitor from Configurator3

    • As long as there is no running PN-Device (application) reachable by the PN-Controller, its red LED will remain on.

    • Additionaly to the detailed GettingStarted manual, We’ve created a clip for you how it might be possible to commissioning the Kunbus Windows Driver of a DF Profinet IO board. Therefore I simply connected Controller port and Device port of a DF Profinet IO board to each. Please ensure the cables are connected properly. The Link-LED of every connected Ethernet port of the board should luminate.

    • Kunbus Example Clip: