DF PROFINET IO | Getting Started (Q+A) - Windows driver

Caption:

  • Question

    • Solution


  • The two device ports still as above, basic device example software started an choice 4 active. If I do not do this the controller finds no devices.

    • An application has to be run on your Profinet-Device, else your device would not be visible since the Profinet-FW is not running on it.

    • That affects any Profinet-Device from any provider.

    • see Kunbus Example Clip below



  • Controller port has IP 192.168.20.1. How can I verify what the IP of the control port actually is without using some external PC / router /…. ?

    • By connecting the DF Profinet IO board directly to a Ethernet port of your Host PC. Then start Kunbus Network Configurator. It will detect the boards Controller IP Addr. .

    • Network Configurator Clip:

  • Every device has to be configured with I/O-Modules in its slots(at least one). What do you mean by slot ?

    • It is necessary to add IN- and/or OUT-Modules to a device to complete its configuration.




  • I get red light on all 3 KUNBUS board ports and “Bad By SubSlot” when I try to monitor from Configurator3

    • As long as there is no running PN-Device (application) reachable by the PN-Controller, its red LED will remain on.

    • Additionaly to the detailed GettingStarted manual, We’ve created a clip for you how it might be possible to commissioning the Kunbus Windows Driver of a DF Profinet IO board. Therefore I simply connected Controller port and Device port of a DF Profinet IO board to each. Please ensure the cables are connected properly. The Link-LED of every connected Ethernet port of the board should luminate.

    • Kunbus Example Clip: