DRAFT
This page shows a few examples of how KUNBUS Gateways can be used in and in combination with RevolutionPi products:
Modular Gateway PROFINET IRT
Modular Gateway EtherCAT
Modular Gateway Ethernet/IP
Connect two PLC together with two KUNBUS Gateways and a RevolutionPi main Module
You can use two gateways in conjunction with a RevolutionPi Core to connect two PLCs.
The advantage of this configuration is:
The RevolutionPi can analyse, process and edit the data before forward it - see RevolutionPi Gateway Tutorial
The PLCs can have different protocols
The configuration is shown in the image below:
You can also do this with the RevolutionPi Connect +/S. For this you can also use a CON module.
Connect Two PLC with different protocols.
You can use two KUNBUS gateways wihout a RevPi Module to connect two devices (PLC) to support different industrial networks.
The configuration is shown in the image below:
Control a RevolutionPi IO-Modules from an external device
You can read or write the inputs/outputs of a Revolution IO-Module via an external device. This can be done with the help of a KUNBUS Gateway module.
A RevolutionPi Core or Connect is also required for this.
The configuration is shown in the image below:
This can also be realized with a CON module.
Additional Information
on each PiBridge, we support a maximum of 5 devices. Only one GW can be used per PiBRidge side, and the gateway must always be the last component.
No gateways or IO modules can be used on the ConBridge. There are special CON modules for this.
The RevolutionPi Core SE and Connect SE do not have GW functionality. This means that no KUNBUS GW can be connected there.
For more information, see the following link.
https://revolutionpi.com/new-s-series-and-se-series/?noredirect=en_USThere are not only physical gateways. We also support virtual gateways such as Modbus RTU and Modbus TCP. Only these two can be used as Slave or as Master.
In the following links you will find some application notes that will help you.
General information