How can we best implement the cabling for a type K thermocouple on the AIO or do we need an additional evaluation unit or something else for this?
The AIO cannot be operated with type K sensors, but only with PT100/PT1000, as you have already mentioned. If you want to use these, you need external transducers to 0-10V / 0-24 mA.
https://revolutionpi.com/forum/viewtopic.php?p=15814#p15814I have a sensor with 4-24 mA voltage, but I can't set the measuring range, what can I do?
Use the measuring range 0-24 mA.
Why does the AIO IN LED sometimes flash even though I have not changed anything?
Try to pull unused analog inputs to GND using a wire jumper. Alternatively, configure the maximum measuring range for this +- 10V.