This is here an article how to start up the Teltonika router, as how digital outputs can be switched.
This is not a KUNBUS product, so we do not provide support for it. If you have any questions, please contact the dealer/company.
What is needed?
Teltonika
Teltonika RUT-955 will act as a Modbus Client. The configuration of the slave is done in the web interface. The web address is 192.168.1.1.
Steps of the configuration Teltonika
Login
Select Services/ Modbus in the menu
Activate Modbus TCP slave as shown in the following picture. Do not forget to save
QModMaster
QModMaster will act as master.
Steps Configure QModMaster as Master
Select Modbus TCP in the Options menu and enter the parameters of the slave (IP address and port).
Pay attention to the settings in the Settings of the Menu Options
Writing and reading the data
The function code for reading is 0x06 → "Write Single Register (0x06)
The function code for writing is 0x06 → "Read Holding Registers (0x03)
Register Address to address the open collector output to enter as Start Address.
The register address for the output (open collector output) is 202 (BOOL⇾ 0|1)
The register address for the relay output PIN is 203 (BOOL⇾ 0|1)
For writing, use the field number 4 as shown in the picture below and press Enter (don't forget!).