Initially please check the used Kunbus-ConfiguratorIII version, logged in the first lines of C:\ProgramData\Configurator3\ABM_TO_DFXX.log
e.g: (the latest version is currently the one of Mar 2019)

ABM to DFXX Converter

Version: 1.6.4.0 - Apr  7 2017
...

Log in ABM_TO_DFXX ends with Perrorline ...

Description

READ_SERIAL_NUMBER NTError = 0x0 Perror = 0x26

Board not reachable. Board may be offline or a wrong resource is chosen.

PARAM_FUNCTION NTError = 0x0 Perror = 0x0

No error occurred. PB-Master works fine.

MANAGE_PROFIBUS_CONF - MPC_READ_CHECKSUM NTError = 0x0 Perror = 0x15

Configuration error while trying access the Master.
(e.g. Perror = 0x15: the Profibus Master is not configurable because its Auto Slave option is activated)

0x0 SUCCESS_0
0x2 MPC_UNKNOWN_COMMAND
0x10 POLL_LIST_ALREADY_RUNNING
0x11 DUPLICATE_PB_ADDRESS
0x12 STORED_IMAGE_IS_INVALID
0x13 DEVICE_IS_NO_PB_MASTER
0x14 HARDWARE_ERROR
0x15 AUTO_SLAVE_ACTIV