Where can I find details on UL certification?

Open the page: Product iQ | UL Solutions (ulprospector.com)

  • Click <Search abridged site without login>

  • Search for "kunbus gmbh"

  • select second entry <NRAQ.E494534>

  • click on <Model Number(s)>

UL Revpi Connect 4-20240307-105455.jpg

 

The technical data of the RevPi Connect 4 is not precise regarding the norm about protection of logic system 4kV/8kV. Can you explain this in more detail?

  • We can provide these answers:

    ESD (EN 61000-4-2) contact discharge: 4kV, air discharge 8kV

    • Surge (EN 61000-4-5): 0.75kV on 24V supply, 0.5kV on RS-485 and Ethernet ports

    • Fast Transients/ Burst (EN 61000-4-4): 2kV on Ethernet, RS485 and 24V

    • Immunity to conducted disturbances, induced by radio-frequency fields (EN 61000-4-6): 150kHz…30MHz / 20V on 24V supply, RS-485 and Ethernet

    • Radiated, radio-frequency, electromagnetic field immunity (EN61000-4-3): 80MHz…1000MHz, 20V/m; 1000MHz…2000MHz, 10V/m; 2000MHz…6000MHz, 10V/m