Part Number: 784041-01
Symptoms summary
Single in the network the communication between master and cRIO ECAT S works.
If more than one slave is operating in the ECAT network, the cRIO ECAT S will abort with the LED status message "Watchdog timeout".
The master is not in DC mode
Instructions
Start the Master (or TwinCAT) in DC-Mode and open the example “DC-VI”.
To start the project for cRIO ECAT S in DC mode, please open the "cRIO ECAT S Getting Started_DC(FPGA).vi" in the sample project. Please start the master with DC switched on before executing the VI.