How to generate a bus record
Action | Additional information |
The Ethernet port of the PC must be integrated into your PROFINET network. | Use a switch to connect your PROFINET network and your Ethernet port. |
Create a local file "command.txt" with the content "watch" in it. |
| ||||||||||||
Open the file Explorer | see video above | |||||||||||
Call ftp://192.168.20.1/ or your IP-Address of the PROFINET board if it differs. | see video above | |||||||||||
Copy the created command.txt to the ftp folder from the step before. | see video above | |||||||||||
After some seconds the file is deleted (refresh folder) | see video above | |||||||||||
Unplug and plug the Ethernet cable on the PROFINET board. This triggers the bus record. | ||||||||||||
On the ftp folder a *.pcap – file appears. | ||||||||||||
In case of using the DF PROFINET IO device: | go online with your PLC and start the PROFINET device | |||||||||||
In case of using the DF PROFINET IO controller | start the PROFINET Controller | |||||||||||
Wait about one minute while the recording will be done | ||||||||||||
Copy the *.pcap file from the board to a local folder and send this file to us. | ||||||||||||
Info: Start a new record by disconnect and connect the Ethernet cable on the PROFINET board again. | ||||||||||||
Set back the DF PRROFINET IO board in normal operation by rebooting your PC. |